Showing all 2 results

  • santronic_dmg970-n_mod01

    DMG 970-N Mod. 01

    Santronic DMG 970-N Mod. 01

    The burner control box DMG 970 controls and supervises power burner for gas and dual fuel. The control box is approved and certified according the relevant European standards.
    The use on direct air heaters according DIN 4794 is also possible. The microprocesso


  • satronic_dmg972mod01

    DMG 972 Mod 01

    TECHNICAL DATA

    Operating voltage 220 / 240 V (-15… +10%) 50 Hz ( ±5%) or 110 / 120 V (-15… +10%) 60 Hz ( ±5%) Fuse rating 10 A fast, 6 A slow Power consumption ca. 12 VA Max. load per output – term. 3 ignition trafo 1.5 A, cos ϕ 0.2 – term. 4 motor 2.0 A, cos ϕ 0.4 – term. 5 + 6 solenoid valves 1.0 A, cos ϕ 0.4 – term. C air damper 1.0 A, cos ϕ 0.4 – term. B alarm indicator 1.0 A, cos ϕ 0.4 total load 5.0 A, cos ϕ 0.4 max. 20 A during 0.5 sec Direct lockout after a loss-of-flame during operation Air proving switch 1 working contact 4 A, 230V Sensitivity (operation) 1 µA Min. required ion. current 1.5 µA Sensitivity for stray light 0.4µA Ionisation probe insulation Probe – earth greater than 50 MΩ stray capacity Probe – earth less than 1000 pF cable lenght < 3 m Flame detectors IRD 1020 side-on or end-on viewing UVD 971 end-on viewing Weight incl. Wiring base 190 g Mounting position any Protection class IP 40 Approved ambient parameter for control and flame detector max. 95% at 30° C – for operation -20° C… +60° C – for storage -20° C… +80° C Build-up of ice, penetration of water and condensing water are inadmissible Approvals according to European standards EN 298 and EN 230, as well as all other relevant Directives and standards Classified acc. to EN 298 FTLLXN