Das IRD 1010 ersetzt die Versionen IRD 810/910/911/911vi (in Verbindung mit Steckerkabel).
-IRD 1010
-axial, weiss
-Passend z.B. für Man, MHG, RE 1 LN/RE2 (Ölbrenner)
– Buderus BRE Ref. 5883617
-MHG-Artikel-Nr. 95.95214-0048
-Hersteller-Nr. 1650206
With this type of flame supervision, the UV radiation emitted by gas or oil flames is used to generate the flame signal.
The radiation detector consists of a UV-sensitive cell with 2 electrodes, which ignite when illuminated with radiation in the 190…270 nm range of the spectrum, thereby triggering a current in the flame detector circuit.
The UV cell does not respond to glowing firebrick in the combustion chamber, daylight or light from the boiler room illumination.